The RCH-800E2JA is a high-capacity water-cooled centrifugal chiller with a nominal cooling capacity of 2,814 kW (800 RT). It is equipped with two liquid-suspended, variable-frequency centrifugal compressors and is designed for large central cooling and process cooling applications. The unit features high efficiency, stable chilled-water outlet temperature control, and a compact overall design, making it suitable for demanding HVAC and industrial cooling systems.
The RCH-800E2JA uses a falling-film / flooded type evaporator and a shell-and-tube condenser, with DN 300 water connections for both heat exchangers. It operates on a 380 V, 3-phase, 50 Hz power supply and provides a chilled-water outlet temperature of 7°C under standard conditions. The unit has a COP of 6.65 kW/kW and an IPLV of 10.12, reflecting high full-load and part-load energy efficiency.
The chiller is driven by two liquid-suspended variable-frequency centrifugal compressors, with a rated current of 325 × 2 A (650 A) and a maximum current of 748 A. Its starting current is only 2 A, helping reduce startup impact on the electrical system. The unit is designed in accordance with GB/T 18430.1-2024, and its energy efficiency is based on GB 19577-2024.

Large cooling capacity: 2,814 kW / 800 RT, suitable for large-scale central cooling systems.
Dual-compressor design: Two liquid-suspended, variable-frequency centrifugal compressors for reliable and flexible operation.
High efficiency: COP of 6.65 kW/kW and IPLV of 10.12.
Low starting current: Starting current of only 2 A, reducing electrical starting impact.
Stable chilled-water outlet temperature: Standard chilled-water outlet temperature of 7°C.
| Parameter | Unit | Specification |
| Performance Parameters | ||
| Cooling Capacity | kW | 2814 |
| Cooling Capacity | RT | 800 |
| Chilled Water Outlet Temperature | °C | 7 |
| Input Power | kW | 211.6 × 2 |
| Power Supply Capacity | kW | 254 × 2 |
| COP | kW/kW | 6.65 |
| IPLV | – | 10.12 |
| Electrical Parameters | ||
| Power Supply | – | 380 V, 3-phase, 50 Hz |
| Starting Current | A | 2 |
| Rated Current | A | 325 × 2 (650) |
| Maximum Current | A | 748 |
| Compressor | ||
| Type | – | Liquid-suspended, variable-frequency centrifugal compressor |
| Quantity | – | 2 |
| Evaporator | ||
| Type | – | Falling-film / flooded type |
| Water Flow Rate | m³/h | 484 |
| Pressure | kPa | 80 |
| Water Connection Size | DN | DN 300 |
| Condenser | ||
| Type | – | Shell-and-tube type |
| Water Flow Rate | m³/h | 605 |
| Pressure | kPa | 70 |
| Water Connection Size | DN | DN 300 |
Energy-saving operation: High COP and IPLV help reduce full-load and part-load energy consumption.
Reduced startup impact: Low starting current supports stable integration with electrical distribution systems.
Operational redundancy and flexibility: Dual compressors allow flexible capacity control and contribute to reliable operation.
Easy system integration: DN 300 water connections and standard 380 V / 3-phase / 50 Hz power supply.
Space-efficient installation: Compact overall dimensions for a high-capacity centrifugal chiller.
The RCH-800E2JA is suitable for large-scale cooling applications, including:
Commercial buildings and large HVAC central cooling systems
Data centers and telecommunication facilities
Hospitals, airports, and large public buildings
District cooling systems
Standard-condition unit parameters are specified in accordance with GB/T 18430.1-2024. Operating conditions: chilled-water outlet temperature 7°C; chilled-water flow rate = cooling capacity × 0.172 m³/(h·kW); cooling-water inlet temperature 30°C; cooling-water flow rate = cooling capacity × 0.215 m³/(h·kW).
The energy-efficiency grade of standard-condition units is based on GB 19577-2024, “Minimum Allowable Values of the Energy Efficiency and Energy Efficiency Grades for Water Chillers.”
The design pressure on the water side of the evaporator and condenser is 1.0 MPa. If the required operating pressure exceeds 1.0 MPa, please specify this when placing the order.